Difference between revisions of "ASM Roof System Details"
Difference between revisions of "ASM Roof System Details"
(34 intermediate revisions by the same user not shown) | |||
Line 1: | Line 1: | ||
− | : | + | {{Template:RPM Info}} |
− | : | + | __NONUMBEREDHEADINGS__ |
+ | {{DISPLAYTITLE:<span style="position: absolute; clip: rect(1px 1px 1px 1px); clip: rect(1px, 1px, 1px, 1px);">{{FULLPAGENAME}}</span>}} | ||
+ | __NOTOC__ | ||
− | <div | + | :<big><big>Division D - Construction Details</big></big> |
− | :[[File:ASM | + | :<hr> |
+ | :<big><big><big><big><big>Construction Details for Architectural Sheet Metal (ASM) Roof Systems</big></big></big></big></big> | ||
+ | |||
+ | <div class="col-md-2"> | ||
+ | :[[File:ASM Project.jpg | link=http://rpm.rcabc.org/images/b/b2/ASM_Project.jpg|175 px]] | ||
</div> | </div> | ||
+ | |||
+ | <div class="col-md-10"> | ||
+ | :The drawings linked on this page are intended to represent a variety of ASM roof system applications while remaining generic with regards to ''manufacturer's'' specific application specifications. They do not represent all possible ''manufacturer'' application roof system designs. Consult each ''manufacturer's'' specifications and the '''''RoofStar Guarantee Standards''''' to develop a system acceptable to both the manufacturer and the '''''RoofStar Guarantee Program'''''. | ||
+ | |||
+ | :For further information about Architectural Sheet Metal Roof System designs and requirements, see the '''[https://rpm.rcabc.org/index.php?title=ASM_Roof_Systems_Standard Standard for Architectural Sheet Metal (ASM) Roof Systems]'''. | ||
+ | </div> | ||
+ | |||
<div class="col-md-12"> | <div class="col-md-12"> | ||
− | |||
− | |||
</div> | </div> | ||
− | ''' | + | <div class="col-md-4"> |
+ | <hr> | ||
+ | ===Part 6 - Air and Vapour Controls=== | ||
+ | ====='''Continuity and Support''' ([[ASM_Roof_Systems_Standard#6.3.2.1._Continuity_and_Support | Article 6.3.2.1.]])===== | ||
+ | <ol> | ||
+ | <li>[[ASM Air and Vapour Controls (Field) | Air and Vapour Controls (Field)]] | ||
+ | </li></ol> | ||
+ | |||
+ | ===Part 8 - Eave, Valley, and Field Underlayment=== | ||
+ | ====='''Eave Protection/Underlayment (Slopes 1:3 or More)''' ([[ASM_Roof_Systems_Standard#8.3.2.1. Installation of Eave Protection | Article 8.3.2.1.]] and [[ASM_Roof_Systems_Standard#8.3.2.3. Underlayment for Common and Steep Slopes | Article 8.3.2.3.]])===== | ||
+ | <ol> | ||
+ | <li>[[ASM Eave Protection and Underlayment | Eave Protection and Underlayment ]] | ||
+ | </li></ol> | ||
+ | |||
+ | ====='''Eave Protection/Underlayment (Slopes Less Than 1:3)''' ([[ASM_Roof_Systems_Standard#8.3.2.1. Installation of Eave Protection | Article 8.3.2.1.]] and [[ASM_Roof_Systems_Standard#8.3.2.4. Underlayment for Slopes Less Than 1:3 | Article 8.3.2.4.]])===== | ||
+ | <ol> | ||
+ | <li>[[ASM Eave Protection and Underlayment (Low Slopes) | Eave Protection and Underlayment (Low Slopes)]] | ||
+ | </li></ol> | ||
+ | |||
</div> | </div> | ||
− | <div class="col-md- | + | <div class="col-md-4"> |
<hr> | <hr> | ||
− | |||
− | < | + | ===Part 10 - Perimeters and Valleys=== |
+ | ====='''Roof-Wall Connections''' ([[ASM_Roof_Systems_Standard#10.3.2.3._General_Application_Requirements_for_Perimeters_and_Walls | Article 10.3.2.3.]])===== | ||
+ | |||
+ | <ol> | ||
+ | <li>[[ASM Roof-Wall Connection (Head-wall) | Roof-Wall Connection (Head-wall)]] | ||
+ | <li>[[ASM Roof-Wall Connection (Head-wall, Vented) | Roof-Wall Connection (Head-wall, Vented)]] | ||
+ | </li></ol> | ||
+ | |||
+ | ====='''Ridges''' ([[ASM_Roof_Systems_Standard#10.3.4.1._Ridges | Article 10.3.4.1.]])===== | ||
− | < | + | <ol> |
+ | <li>[[ASM Ridge (Unvented, Uninsulated) | Ridge (Unvented, Uninsulated)]] | ||
+ | <li>[[ASM Ridge (Unvented, Insulated) | Ridge (Unvented, Insulated)]] | ||
+ | <li>[[ASM Ridge (Vented, Uninsulated) | Ridge (Vented, Uninsulated)]] | ||
+ | </li></ol> | ||
− | < | + | ====='''Eave and Rake Edge Details''' ([[ASM_Roof_Systems_Standard#10.3.4.2._Eaves_and_Rake_Edges | Article 10.3.4.2.]])===== |
+ | <ol> | ||
+ | <li>[[ASM Eave and Rake Edges (Mechanical Seams) | Eave and Rake Edges (Mechanical Seams)]] | ||
+ | <li>[[ASM Eave and Rake Edges (Snap-Lock Seams) | Eave and Rake Edges (Snap-Lock Seams)]] | ||
+ | <li>[[ASM Eave and Rake Edges (Copper) | Eave and Rake Edges (Copper)]] | ||
+ | <li>[[ASM Eave and Rake Edges (Zinc) | Eave and Rake Edges (Zinc)]] | ||
+ | </li></ol> | ||
− | + | ====='''Valleys''' ([[ASM_Roof_Systems_Standard#10.3.5.2._General_Requirements_for_Valley_Metal_Flashing | Article 10.3.5.2.]])===== | |
− | < | + | <ol> |
+ | <li>[[ASM Valley (Hooked) | Valley (Hooked)]] | ||
+ | <li>[[ASM Valley (Unhooked) | Valley (Unhooked)]] | ||
+ | </li></ol> | ||
</div> | </div> | ||
− | <div class="col-md- | + | <div class="col-md-4"> |
<hr> | <hr> | ||
− | |||
− | < | + | ===Part 11 - Drainage=== |
− | + | ====='''Membrane Gutters''' ([[ASM_Roof_Systems_Standard#11.3.3.8._Membrane_Gutters | Article 11.3.3.8.]])===== | |
− | + | ||
− | < | + | <ol> |
+ | <li>[[ASM Membrane Gutter (Design Elements) | Membrane Gutter (Design Elements)]] | ||
+ | <li>[[ASM Membrane Gutter (Insulated Assembly) | Membrane Gutter (Insulated Assembly)]] | ||
+ | </li></ol> | ||
+ | |||
+ | ===Part 12 - Penetrations and Curbs=== | ||
+ | ====='''Penetration Flashing''' ([[ASM_Roof_Systems_Standard#12.3.2.1._General_Requirements_for_Flashing_Penetrations | Article 12.3.2.1.]])===== | ||
+ | |||
+ | <ol> | ||
+ | <li>[[ASM Cylindrical Penetration (Flexible Boot Flashing) | Cylindrical Penetration (Flexible Boot Flashing)]] | ||
+ | <li>[[ASM Cylindrical Penetration (Split Panel Flashing) | Cylindrical Penetration (Split Panel Flashing)]] | ||
+ | </li></ol> | ||
+ | |||
+ | ====='''Curbs''' ([[ASM_Roof_Systems_Standard#12.3.2.4._Curbs_and_Sleepers | Article 12.3.2.4.]])===== | ||
+ | |||
+ | <ol> | ||
+ | <li>[[ASM Curb (Split Panel Flashing) | Curb (Split Panel Flashing)]] | ||
+ | </li></ol> | ||
− | + | ===Part 13 - Linear Metal Flashing=== | |
− | + | :See the separate page, [[Linear_Metal_Flashing_Details | Details for Linear Metal Flashings]]. | |
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | : | ||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
</div> | </div> | ||
+ | |||
<div class="col-md-12"> | <div class="col-md-12"> | ||
+ | <hr> | ||
+ | [[ASM Roof Systems Standard|<i class="fa fa-chevron-circle-left" ></i> ''Standard for ASM Roof Systems'']] | ||
− | + | [[Main Page | <i class="fa fa-home fa"></i> Home]] | |
− | [[ | + | {{Template:RPM Page Footer with Copyright and Current Date}} |
− | |||
− | |||
</div> | </div> |
Latest revision as of 20:11, 28 June 2022
- Division D - Construction Details
- Construction Details for Architectural Sheet Metal (ASM) Roof Systems
- The drawings linked on this page are intended to represent a variety of ASM roof system applications while remaining generic with regards to manufacturer's specific application specifications. They do not represent all possible manufacturer application roof system designs. Consult each manufacturer's specifications and the RoofStar Guarantee Standards to develop a system acceptable to both the manufacturer and the RoofStar Guarantee Program.
- For further information about Architectural Sheet Metal Roof System designs and requirements, see the Standard for Architectural Sheet Metal (ASM) Roof Systems.
Part 6 - Air and Vapour Controls
Continuity and Support ( Article 6.3.2.1.)
Part 8 - Eave, Valley, and Field Underlayment
Eave Protection/Underlayment (Slopes 1:3 or More) ( Article 8.3.2.1. and Article 8.3.2.3.)
Eave Protection/Underlayment (Slopes Less Than 1:3) ( Article 8.3.2.1. and Article 8.3.2.4.)
Part 10 - Perimeters and Valleys
Roof-Wall Connections ( Article 10.3.2.3.)
Ridges ( Article 10.3.4.1.)
Eave and Rake Edge Details ( Article 10.3.4.2.)
- Eave and Rake Edges (Mechanical Seams)
- Eave and Rake Edges (Snap-Lock Seams)
- Eave and Rake Edges (Copper)
- Eave and Rake Edges (Zinc)
Valleys ( Article 10.3.5.2.)
Part 11 - Drainage
Membrane Gutters ( Article 11.3.3.8.)
Part 12 - Penetrations and Curbs
Penetration Flashing ( Article 12.3.2.1.)
Curbs ( Article 12.3.2.4.)
Part 13 - Linear Metal Flashing
- See the separate page, Details for Linear Metal Flashings.
© RCABC 2024
RoofStarTM is a registered Trademark of the RCABC.
No reproduction of this material, in whole or in part, is lawful without the expressed permission of the RCABC Guarantee Corp.