#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements. | #'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements. | ||
− | #'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php/ | + | #'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php/RoofStar_Guarantee_Standards_for_ASM_Systems RoofStar Guarantee Standards for ASM Systems]. |
<hr> | <hr> |
Revision as of 21:50, 28 April 2020
The metal panel listed and described below is accepted for use in the RoofStar Guarantee Program. |
The roofing assembly / material information published below and in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority. For more information about this product or system, consult the manufacturer. |
OVERVIEW
The Knudson KR-24 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 38 mm (1 1/2"). Panels are produced with two stiffening flutes.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
SYSTEM DESCRIPTION
- General: Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
- Range of application: On wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- Fasteners (Screws):
- Wood Decks: Fasteners to be #10 x 22 mm (1") long pancake head type A plated.
- Steel Decks: Fasteners to be #8-16 x 22 mm (1") long self-drilling, self tapping wafer head, plated screws.
- Panel Clips:
- Wood Decks:
- Panel clip to be Knudson 22 ga one piece assembly 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 762 mm (30") on centre. Two fasteners per panel clip used, inserted into panel clip guide holes. Fasteners to be #10 x 22 mm (1") long pancake head type A plated.
- Two piece assembly to be used for longer panel lengths, clip to be Knudson 22 ga 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre.
- Steel Decks:
- Panel clip to be Knudson 22 ga one piece assembly 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre. Two fasteners per panel clip used, inserted into panel clip guide holes. Fasteners to be #8-16 x 22 mm (1") long self-drilling, self tapping wafer head, plated screws.
- Two piece assembly to be used for longer panel lengths, clip to be Knudson 22 ga 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre.
- Wood Decks:
PROFILE
N/A
TECHNICAL DATA SHEET
N/A
SITE CONDITIONS
Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
PERFORMANCE REQUIREMENTS
- Wind Uplift Standards: Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also Guides and Notes (Wind Resistance) for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
- Materials:RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the RoofStar Guarantee Standards for ASM Systems.