Line 30: Line 30:
 
##Two-part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") O.C. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16") Knudson Manufacturing Inc. - "KR-24 Low-Floating Clip" or "KR-24 High-Floating Clip."
 
##Two-part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") O.C. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16") Knudson Manufacturing Inc. - "KR-24 Low-Floating Clip" or "KR-24 High-Floating Clip."
 
##One-part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3") Knudson Manufacturing Inc. - "KR-24 Low-Fixed Clip" or "KR-24 High-Fixed Clip", fastened 600 mm (24") O.C.
 
##One-part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3") Knudson Manufacturing Inc. - "KR-24 Low-Fixed Clip" or "KR-24 High-Fixed Clip", fastened 600 mm (24") O.C.
 +
#'''Deck Requirements''': in keeping with the [http://rpm.rcabc.org/index.php?title=Standard_for_Architectural_Sheet_Metal_(ASM)_Systems Standard for Architectural Sheet Metal (ASM) Systems].
  
 
====PROFILE====
 
====PROFILE====
Line 42: Line 43:
 
====PERFORMANCE REQUIREMENTS====
 
====PERFORMANCE REQUIREMENTS====
 
#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
 
#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
#'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php/RoofStar_Guarantee_Standards_for_ASM_Systems RoofStar Guarantee Standards for ASM Systems].
+
#'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php?title=Standard_for_Architectural_Sheet_Metal_(ASM)_Systems Standard for Architectural Sheet Metal (ASM) Systems].
  
 
<hr>
 
<hr>

Revision as of 17:16, 24 June 2021


The metal panel listed and described below is accepted for use in the RoofStar Guarantee Program.
Manufacturer
Aurora Roofing Ltd.
Contact Address
See the current Membership list and contact information at www.rcabc.org
Product Group - Standing Seam Metal Roof System
Panel Machine
Knudson
Panel Name
Knudson KR-12
Seam Type
Mechanical Lock

The roofing assembly / material information published below and in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority. For more information about this product or system, consult the manufacturer.

OVERVIEW

The Knudson KR-12 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 38 mm (1 1/2").

On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').

SYSTEM DESCRIPTION

  1. General: Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
  2. Range of application: On wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
  3. Fasteners (Screws): Panel clip to steel attachment to be No. 12-16 by 22 mm (1") long self- drilling, self-tapping, hex-washer head plated steel screws used without sealing washers. Two fasteners per panel clip used, inserted into panel clip guide holes.
  4. Panel Clips:
    1. Two-part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") O.C. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16") Knudson Manufacturing Inc. - "KR-24 Low-Floating Clip" or "KR-24 High-Floating Clip."
    2. One-part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3") Knudson Manufacturing Inc. - "KR-24 Low-Fixed Clip" or "KR-24 High-Fixed Clip", fastened 600 mm (24") O.C.
  5. Deck Requirements: in keeping with the Standard for Architectural Sheet Metal (ASM) Systems.

PROFILE

N/A

TECHNICAL DATA SHEET

N/A

SITE CONDITIONS

Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").

PERFORMANCE REQUIREMENTS

  1. Wind Uplift Standards: Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also Guides and Notes (Wind Resistance) for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
  2. Materials:RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the Standard for Architectural Sheet Metal (ASM) Systems.