:#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements. | :#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements. | ||
− | :#'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http:// | + | :#'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php/RoofStar_Guarantee_Standards_for_ASM_Roof_Assemblies Architectural Sheet Metal (ASM) Roof Standards]. |
<hr> | <hr> |
Revision as of 17:01, 24 September 2018
Manufacturer: LAM METAL CONTRACTING LTD.
Contact Address: See the current Membership list and contact information at www.rcabc.org
Product Group: SNAP LOCK SEAM METAL ROOF SYSTEM – SNAP-LOC NU-TECH
- DESCRIPTION
The Snap-Loc Nu-Tech is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 457 mm (18") wide with a 44 mm (1 3/4") rib.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 The Snap-Loc Nu-Tech 44 mm (1 3/4") is a snap lock concealed fastener roofing panel. The panel can be formed in any width between 300 mm (12") to 457 mm (18"). Stiffening ribs, striations and / or clip relief can be added depending on the application. The male leg locks along the entire length of the panel and does not rely upon clips to provide additional locking. The Snap-Loc Nu-Tech utilizes 153 mm (6 1/8") of metal in forming the panel legs providing greater structural integrity, which can carry greater loads.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to steel to be No. 10-16 by 25 mm (1") long cadmium plated pancake head No. 2 Phillips drive, No. 3 self-drilling points steel screws. Two screws per clip inserted through 6.25 mm (1/4") diameter guide holes.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly, No. 22 MSG min thick, 88 mm (3 1/2") high. One panel clip spaced at 600 mm (24") on centre for Class 90.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- Wind Uplift Standards: Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also Guides and Notes (Wind Resistance) for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
- Materials:RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the Architectural Sheet Metal (ASM) Roof Standards.