| style="background-color: #ffffcc; column-width:100%" | The metal panel listed and described below is accepted for use in the '''''RoofStar Guarantee Program'''''.
 +
|}
 +
{| class="wikitable"
 +
|-
 +
|
 +
;'''Manufacturer''': Aurora Roofing Ltd.
 +
;'''Contact Address''': See the current Membership list and contact information at [http://www.rcabc.org/members/find-a-member/ www.rcabc.org]
 +
;'''Product Group - Standing Seam Metal Roof System''': Knudson KR-12
  
<i>Contact Address:</i> See the current Membership list and contact information at [http://www.rcabc.org/members/find-a-member/ '''www.rcabc.org''']
+
The roofing assembly / material information published below and in the [http://{{SERVERNAME}}/index.php?title=Main_Page RCABC Roofing Practices Manual] DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority. For more information about this product or system, consult the manufacturer.
 +
|}
  
<i>Product Group: <b>STANDING SEAM METAL ROOF SYSTEM - Knudson KR-12</b></i>
+
====OVERVIEW====
 +
The Knudson KR-12 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 38 mm (1 1/2").
  
;<u>DESCRIPTION</u>
+
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
  
:The Knudson KR-12 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 38 mm (1 1/2").  
+
====SYSTEM DESCRIPTION====
 +
#'''General''': Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
 +
#'''Range of application''': On wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
 +
#'''Panel Attachment''': 
 +
::# '''Fasteners (Screws)''': Panel clip to steel attachment to be No. 12-16 by 22 mm (1") long self- drilling, self-tapping, hex-washer head plated steel screws used without sealing washers. Two fasteners per panel clip used, inserted into panel clip guide holes.  
 +
::# '''Roof Deck Fasteners (Panel Clips)''':
 +
:::*Two part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") on centre. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16") Knudson Manufacturing Inc. &#8211; &#8220;KR-24 Low-Floating Clip&#8221;, &#8220;KR-24 High-Floating Clip&#8221;OR
 +
:::*One part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3") Knudson Manufacturing Inc. &#8211; &#8220;KR-24 Low-Fixed Clip&#8221;, &#8220;KR-24 High-Fixed Clip&#8221;. Fastened 600 mm (24") on centre.
  
:On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
+
====PROFILE====
 +
N/A
  
1.1 <u>GENERAL</u>
+
====TECHNICAL DATA SHEET====
 +
N/A
  
:The roofing assembly / material information published in the RGC <i>Roofing Practices Manual</i> DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
+
====SITE CONDITIONS====
 +
Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").  
  
1.2. <u>SYSTEM DESCRIPTION</u>
+
====PERFORMANCE REQUIREMENTS====
 
+
#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
:.1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
+
#'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php/RoofStar_Guarantee_Standards_for_ASM_Roof_Assemblies RoofStar Guarantee Standards for ASM Roof Assemblies].
 
 
:.2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
 
 
 
:.3 Panel Attachment:
 
:;Fasteners (Screws)
 
::For panel clip to steel attachment to be No. 12-16 by 22 mm (1") long self- drilling, self-tapping, hex-washer head plated steel screws used without sealing washers. Two fasteners per panel clip used, inserted into panel clip guide holes.
 
 
 
:;Roof Deck Fastener (Panel clip)
 
::Two part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") on centre. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16") Knudson Manufacturing Inc. &#8211; &#8220;KR-24 Low-Floating Clip&#8221;, &#8220;KR-24 High-Floating Clip&#8221;OR
 
 
 
::One part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3") Knudson Manufacturing Inc. &#8211; &#8220;KR-24 Low-Fixed Clip&#8221;, &#8220;KR-24 High-Fixed Clip&#8221;. Fastened 600 mm (24") on centre.
 
 
 
1.3 <u>SITE CONDITIONS</u>
 
:.1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
 
 
 
;1.4 <u>PERFORMANCE REQUIREMENTS</u>
 
 
 
:#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
 
:#'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php/RoofStar_Guarantee_Standards_for_ASM_Roof_Assemblies Architectural Sheet Metal (ASM) Roof Standards].
 
  
 
<hr>
 
<hr>

Revision as of 17:42, 25 September 2018


The metal panel listed and described below is accepted for use in the RoofStar Guarantee Program.
Manufacturer
Aurora Roofing Ltd.
Contact Address
See the current Membership list and contact information at www.rcabc.org
Product Group - Standing Seam Metal Roof System
Knudson KR-12

The roofing assembly / material information published below and in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority. For more information about this product or system, consult the manufacturer.

OVERVIEW

The Knudson KR-12 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 38 mm (1 1/2").

On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').

SYSTEM DESCRIPTION

  1. General: Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
  2. Range of application: On wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
  3. Panel Attachment:
  1. Fasteners (Screws): Panel clip to steel attachment to be No. 12-16 by 22 mm (1") long self- drilling, self-tapping, hex-washer head plated steel screws used without sealing washers. Two fasteners per panel clip used, inserted into panel clip guide holes.
  2. Roof Deck Fasteners (Panel Clips):
  • Two part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") on centre. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16") Knudson Manufacturing Inc. – “KR-24 Low-Floating Clip”, “KR-24 High-Floating Clip”OR
  • One part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3") Knudson Manufacturing Inc. – “KR-24 Low-Fixed Clip”, “KR-24 High-Fixed Clip”. Fastened 600 mm (24") on centre.

PROFILE

N/A

TECHNICAL DATA SHEET

N/A

SITE CONDITIONS

Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").

PERFORMANCE REQUIREMENTS

  1. Wind Uplift Standards: Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also Guides and Notes (Wind Resistance) for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
  2. Materials:RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the RoofStar Guarantee Standards for ASM Roof Assemblies.