Manufacturer: <b>MARINE ROOFING (1996) LTD.</b>
+
__NOTOC__
 +
__NONUMBEREDHEADINGS__
 +
{| class="wikitable"
 +
|-
 +
| style="background-color: #ffffcc; column-width:100%" | The metal panel listed and described below is accepted for use in the '''''RoofStar Guarantee Program'''''.
 +
|}
 +
{| class="wikitable"
 +
|-
 +
|
 +
;'''Manufacturer''': Marine Roofing (1996) Ltd.
 +
;'''Contact Address''': See the current Membership list and contact information at [http://www.rcabc.org/members/find-a-member/ www.rcabc.org]
 +
;'''Product Group - Standing Seam Metal Roof System'''
 +
;'''Panel Machine''': New Tech Machinery
 +
;'''Panel Name''': MR/S-150
 +
;'''Seam Type''': Mechanical Lock
  
Contact Address: See the current Membership list and contact information at [http://www.rcabc.org/members/find-a-member/ '''www.rcabc.org''']
+
The roofing assembly / material information published below and in the [http://{{SERVERNAME}}/index.php?title=Main_Page RCABC Roofing Practices Manual] DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority. For more information about this product or system, consult the manufacturer.
 
+
|}
Product Group: <b>STANDING SEAM METAL ROOF SYSTEM &#8211; MR/S-150</b>
 
 
 
;DESCRIPTION
 
  
 +
====OVERVIEW====
 
The New Tech Machinery Panel Machine is an on-site continuous panel metal roofing machine. This machine produces MR/S-150 panels with a seam height of 38 mm (1-1/2"). Panel profiles vary from 300 mm (12") to 500mm (20") wide.  
 
The New Tech Machinery Panel Machine is an on-site continuous panel metal roofing machine. This machine produces MR/S-150 panels with a seam height of 38 mm (1-1/2"). Panel profiles vary from 300 mm (12") to 500mm (20") wide.  
  
 
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
 
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
 +
====SYSTEM DESCRIPTION====
 +
#'''General''': Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together with the clips as part of the seam, by use of a mechanical seamer.
 +
#'''Range of application''': on wood or metal sloped roofs with or without exterior insulation; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
 +
#'''Fasteners (Screws)''': Fasteners used to attach panel clips to steel to be No. 10-16 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated screw. Minimum two fasteners per clip to be used.
 +
#'''Panel Clips''': One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022". (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert "series 1000 Interlocking Clip".
 +
#'''Deck Requirements''': in keeping with the [http://rpm.rcabc.org/index.php/RoofStar_Guarantee_Standards_for_ASM_Systems RoofStar Guarantee Standards for ASM Systems].
  
;1.1 <u>GENERAL</u>
+
====PROFILE====
:The roofing assembly / material information published in the <b>RCABC <i>Roofing Practices Manual</i></b> DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
+
N/A
  
;1.2 <u>SYSTEM DESCRIPTION</u>
+
====TECHNICAL DATA SHEET====
:.1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together with the clips as part of the seam, by use of a mechanical seamer.
+
N/A
:.2 Range of application: on wood or metal sloped roofs with or without exterior insulation; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
 
:;.3 <b>Panel Attachment:</b>
 
:;<u>Fasteners (Screws)</u>
 
::Fasteners used to attach panel clips to steel to be No. 10-16 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated screw. Minimum two fasteners per clip to be used.
 
:;<u>Roof Deck Fasteners (Panel Clips)</u>
 
::One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022". (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert "series 1000 Interlocking Clip".
 
  
;1.3 <u>SITE CONDITIONS</u>
+
====SITE CONDITIONS====
:.1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").  
+
#Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").  
  
;1.4 <u>PERFORMANCE REQUIREMENTS</u>
 
  
:#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
+
====PERFORMANCE REQUIREMENTS====
:#'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php/RoofStar_Guarantee_Standards_for_ASM_Roof_Assemblies Architectural Sheet Metal (ASM) Roof Standards].
+
#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
 +
#'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php/RoofStar_Guarantee_Standards_for_ASM_Systems RoofStar Guarantee Standards for ASM Systems].
  
 
<hr>
 
<hr>

Revision as of 22:15, 28 April 2020


The metal panel listed and described below is accepted for use in the RoofStar Guarantee Program.
Manufacturer
Marine Roofing (1996) Ltd.
Contact Address
See the current Membership list and contact information at www.rcabc.org
Product Group - Standing Seam Metal Roof System
Panel Machine
New Tech Machinery
Panel Name
MR/S-150
Seam Type
Mechanical Lock

The roofing assembly / material information published below and in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority. For more information about this product or system, consult the manufacturer.

OVERVIEW

The New Tech Machinery Panel Machine is an on-site continuous panel metal roofing machine. This machine produces MR/S-150 panels with a seam height of 38 mm (1-1/2"). Panel profiles vary from 300 mm (12") to 500mm (20") wide.

On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').

SYSTEM DESCRIPTION

  1. General: Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together with the clips as part of the seam, by use of a mechanical seamer.
  2. Range of application: on wood or metal sloped roofs with or without exterior insulation; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
  3. Fasteners (Screws): Fasteners used to attach panel clips to steel to be No. 10-16 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated screw. Minimum two fasteners per clip to be used.
  4. Panel Clips: One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022". (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert "series 1000 Interlocking Clip".
  5. Deck Requirements: in keeping with the RoofStar Guarantee Standards for ASM Systems.

PROFILE

N/A

TECHNICAL DATA SHEET

N/A

SITE CONDITIONS

  1. Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").


PERFORMANCE REQUIREMENTS

  1. Wind Uplift Standards: Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also Guides and Notes (Wind Resistance) for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
  2. Materials:RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the RoofStar Guarantee Standards for ASM Systems.