Materials:(Flynn) Knudson P-2406

Jump to: navigation, search

Materials:(Flynn) Knudson P-2406

Revision as of 16:54, 24 September 2018 by James Klassen (talk | contribs)

Manufacturer: FLYNN CANADA LTD.

Contact Address: See the current Membership list and contact information at www.rcabc.org

Product Group: STANDING SEAM METAL ROOF SYSTEM – KNUDSON P-2406

DESCRIPTION

The Knudson P-2406 is an on-site continuous metal roll forming machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 38 mm (1.5"). Panels are produced with two stiffening flutes.

On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities.

1.1 GENERAL
The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
.1 Architectural standing seam panels employ a hidden fastening system for securing to a solid substrate. Panels are seamed together with a mechanical seamer.
.2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
.3 Panel Attachment: Wood
Panel clip to be Knudson 22 ga one piece assembly 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre. Two fasteners per panel clip used, inserted into panel clip guide holes. Fasteners to be #10 x 22 mm (1") long pancake head type A plated.
Two piece assembly to be used for longer panel lengths, clip to be Knudson 22 ga 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre.
Panel Attachment: Steel
Panel clip to be Knudson 22 ga one piece assembly 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre. Two fasteners per panel clip used, inserted into panel clip guide holes. Fasteners to be #8-16 x 22 mm (1") long self-drilling, self tapping wafer head, plated screws.
Two piece assembly to be used for longer panel lengths, clip to be Knudson 22 ga 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre.
1.3 SITE CONDITIONS
.1 Minimum roof slope is 1:6 (2" in 12").
1.4 PERFORMANCE REQUIREMENTS
  1. Wind Uplift Standards: Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also Guides and Notes (Wind Resistance) for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
  2. Materials:RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the Architectural Sheet Metal (ASM) Roof Standards.