Manufacturer | Product Name | Number of Tested Systems (per report) |
kPa (Low) | kPa (High) | Psf (Low) | Psf (High) | Deck Type | Downloadable Test Report |
---|---|---|---|---|---|---|---|---|
Henry Company Canada | ModifiedPLUS NP250g T4 | 1 Tested System 1 Tested System |
---- ---- |
-3.80 -4.79 |
---- ---- |
-80.00 -100.00 |
Steel Steel |
AARS Test Report 1 AARS Test Report 2 |
IKO Industries Ltd. | Armourcool Granular TP-HD Cap | 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
IKO Industries Ltd. | Modiflex MP-180 Cap | 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
IKO Industries Ltd. | Modiflex MP-250 Cap | 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
IKO Industries Ltd. | Modiflex MP-HD-Cap | 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
IKO Industries Ltd. | Torchflex TP-180 Cap | 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
IKO Industries Ltd. | Torchflex TP-250 Cap 5 mm | 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
IKO Industries Ltd. | Torchflex TP-250 Cap | 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
IKO Industries Ltd. | Torchflex TP-HD-Cap | 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
IKO Industries Ltd. | Prevent TP 250 Cap 4 mm | 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
IKO Industries Ltd. | Prevent TP-HD-Cap | 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
IKO Industries Ltd. | Prevent Premium TP 250 Cap 4 mm | 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
Soprema Inc. | Colply Traffic Cap 460 | 1 Tested System 1 Tested System |
---- ---- |
-3.00 -2.40 |
---- ---- |
-63.00 -50.00 |
Steel Steel |
AARS Test Report 4 AARS Test Report 5 |
Soprema Inc. | Colply Traffic Cap FR 461 | 1 Tested System 1 Tested System |
---- ---- |
-3.00 -2.40 |
---- ---- |
-63.00 -50.00 |
Steel Steel |
AARS Test Report 4 AARS Test Report 5 |
Soprema Inc. | Soprafix Traffic Cap 660 | 1 Tested System 1 Tested System |
---- ---- |
-2.90 -2.70 |
---- ---- |
-58.20 -55.50 |
Steel Steel | AARS Test Report 1 AARS Test Report 2 |
Soprema Inc. | Soprafix Traffic Cap FR 661 | 1 Tested System 1 Tested System |
---- ---- |
-2.90 -2.70 |
---- ---- |
-58.20 -55.50 |
Steel Steel | AARS Test Report 1 AARS Test Report 2 |
Soprema Inc. | Sopralene 180 GR | 1 Tested System 1 Tested System |
---- ---- |
-3.00 -2.40 |
---- ---- |
-63.00 -50.00 |
Steel Steel |
AARS Test Report 4 AARS Test Report 5 |
Soprema Inc. | Sopralene 250 GR | 1 Tested System 1 Tested System |
---- ---- |
-3.00 -2.40 |
---- ---- |
-63.00 -50.00 |
Steel Steel |
AARS Test Report 4 AARS Test Report 5 |
Soprema Inc. | Sopralene Flam 180 GR | 1 Tested System 1 Tested System 1 Tested System 1 Tested System 2 Tested Systems 1 Tested System 3 Tested Systems 2 Tested Systems 3 Tested Systems 2 Tested Systems 1 Tested System 1 Tested System |
---- ---- ---- ---- -3.40 ---- -2.40 -1.90 -3.60 -3.60 ---- ---- |
-2.90 -2.70 -3.00 -4.30 -4.80 -3.00 -4.60 -3.90 -4.30 -3.80 -2.40 -2.40 |
---- ---- ---- ---- -72.00 ---- -50.00 -40.00 -75.00 -75.00 ---- ---- |
-58.20 -55.50 -63.00 -90.00 -100.00 -62.00 -96.00 -83.00 -90.00 -80.00 -50.00 -50.00 |
Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 6 AARS Test Report 7 AARS Test Report 8 AARS Test Report 9 AARS Test Report 10 AARS Test Report 11 AARS Test Report 12 AARS Test Report 13 AARS Test Report 14 AARS Test Report 15 |
Soprema Inc. | Sopralene Flam 250 GR | 1 Tested System 1 Tested System 1 Tested System 1 Tested System 1 Tested System 2 Tested Systems 1 Tested System 3 Tested Systems 2 Tested Systems 3 Tested Systems 2 Tested Systems 1 Tested System 1 Tested System |
---- ---- ---- ---- ---- -3.40 ---- -2.40 -1.90 -3.60 -3.60 ---- ---- |
-2.90 -2.70 -2.90 -3.00 -4.30 -4.80 -3.00 -4.60 -3.90 -4.30 -3.80 -2.40 -2.40 |
---- ---- ---- ---- ---- -72.00 ---- -50.00 -40.00 -75.00 -75.00 ---- ---- |
-58.20 -55.50 -60.00 -63.0 -90.00 -100.00 -62.00 -96.00 -83.00 -90.00 -80.00 -50.00 -50.00 |
Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 AARS Test Report 6 AARS Test Report 7 AARS Test Report 8 AARS Test Report 9 AARS Test Report 10 AARS Test Report 11 AARS Test Report 12 AARS Test Report 13 AARS Test Report 14 AARS Test Report 15 |
Soprema Inc. | Sopraply Traffic Cap FR 561 | 1 Tested System 1 Tested System 1 Tested System 2 Tested Systems 1 Tested System 3 Tested Systems 2 Tested Systems 3 Tested Systems 2 Tested Systems 1 Tested System 1 Tested System |
---- ---- ---- -3.40 ---- -2.40 -1.90 -3.60 -3.60 ---- ---- |
-2.90 -2.70 -4.30 -4.80 -3.00 -4.60 -3.90 -4.30 -3.80 -2.40 -2.40 |
---- ---- ---- -72.00 ---- -50.00 -40.00 -75.00 -75.00 ---- ---- |
-58.20 -55.50 -90.00 -100.00 -62.00 -96.00 -83.00 -90.00 -80.00 -50.00 -50.00 |
Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 7 AARS Test Report 8 AARS Test Report 9 AARS Test Report 10 AARS Test Report 11 AARS Test Report 12 AARS Test Report 13 AARS Test Report 14 AARS Test Report 15 |
Soprema Inc. | SopraStar Flam HD GR | 1 Tested System 1 Tested System 1 Tested System 1 Tested System 2 Tested Systems 1 Tested System 3 Tested Systems 2 Tested Systems 3 Tested Systems 2 Tested Systems 1 Tested System 1 Tested System |
---- ---- ---- ---- -3.40 ---- -2.40 -1.90 -3.60 -3.60 ---- ---- |
-2.90 -2.70 -3.00 -4.30 -4.80 -3.00 -4.60 -3.90 -4.30 -3.80 -2.40 -2.40 |
---- ---- ---- ---- -72.00 ---- -50.00 -40.00 -75.00 -75.00 ---- ---- |
-58.20 -55.50 -63.00 -90.00 -100.00 -62.00 -96.00 -83.00 -90.00 -80.00 -50.00 -50.00 |
Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 6 AARS Test Report 7 AARS Test Report 8 AARS Test Report 9 AARS Test Report 10 AARS Test Report 11 AARS Test Report 12 AARS Test Report 13 AARS Test Report 14 AARS Test Report 15 |