Materials:(Lam) SS 200 Standing Seam (50 mm)
Materials:(Lam) SS 200 Standing Seam (50 mm)
The metal panel listed and described below is accepted for use in the RoofStar Guarantee Program. |
The roofing assembly / material information published below and in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority. For more information about this product or system, consult the manufacturer. |
OVERVIEW
The SS 200 standing seam panel is formed with an in-shop continuous metal roofing panel roll forming machine SSP. This machine produces a standing seam panel with a seam height of 50 mm (2"). Profiles can vary from 305 mm (12") wide to 610 mm (24") wide.
This machine also produces a 44 mm (1-3/4") high Nu-Tech panel profile.
SYSTEM DESCRIPTION
- General: The SS 200 panel is a standing seam concealed fastener roofing panel. The maximum spacing of the clips is 610 mm (2") O.C.
- Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- Fasteners (Screws):
- Fasteners (screws) used to attach panels to plywood deck to be No. 10-12 by 19 mm (5/8") long pancake head wood screw. Minimum two fasteners per clip to be used.
- Two-piece assembly consists of a steel base approximately 127 mm (5") wide x 25 mm (1") long, with a minimum thickness of 0.026 (No. 24 MSG) and an upper tab that measures 50 mm high with a minimum thickness of 0.020 (No. 26 MSG). One panel clip spaced at 610 mm (24") O.C. maximum.
- Fabrication: Unless otherwise shown on drawings or specified herein, fabricate panels in continuous one piece lengths and fabricate flashings and accessories in longest practical lengths.
- Deck Requirements: in keeping with the Standard for Architectural Sheet Metal (ASM) Systems.
PROFILE
SS 200 Standing Seam Panel |
---|
DELIVERY, STORAGE & HANDLING
- Protect against damage and discoloration.
- Handle panels with non-marring slings.
- Do not bend panels.
- Store panels above ground, with one end elevated for drainage.
- Protect panels against standing water and condensation between adjacent surfaces.
- If panels become wet, immediately separate sheets, wipe dry with clean cloth, allow to air dry.
FIELD MEASUREMENTS
- Verify prior to fabrication.
- If field measurements differ from drawing dimensions, notify Architect / Professional Engineer prior to fabrication.
PROTECTION
Treat, or isolate with protective material, any contacting surfaces of dissimilar materials to prevent electrolytic corrosion.
PROFILE
N/A
TECHNICAL DATA SHEET
N/A
SITE CONDITIONS
- Minimum roof slope is 1:6 (2" in 12").
- Verify that structural deck to receive panels is complete, in true plane, secure and otherwise properly prepared.
- Prior to starting work, notify General Contractor about defects requiring correction.
- Do not start work until conditions are satisfactory.
PERFORMANCE REQUIREMENTS
- Wind Uplift Standards: Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also Guides and Notes (Wind Resistance) for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
- Materials:RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the Standard for Architectural Sheet Metal (ASM) Systems.