Difference between revisions of "Materials:(Cascade) Zimmerman SS1500"

Jump to: navigation, search

Difference between revisions of "Materials:(Cascade) Zimmerman SS1500"

(PERFORMANCE REQUIREMENTS)
 
Line 46: Line 46:
  
 
====PERFORMANCE REQUIREMENTS====
 
====PERFORMANCE REQUIREMENTS====
#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
+
<ol>
#'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php?title=Standard_for_Architectural_Sheet_Metal_(ASM)_Systems Standard for Architectural Sheet Metal (ASM) Systems].
+
<li>'''Wind Uplift Resistance''': Panel securement shall conform to the requirements in [https://rpm.rcabc.org/index.php?title=ASM_Roof_Systems_Standard#PART_3 Part 3] of the [http://rpm.rcabc.org/index.php?title=Standard_for_Architectural_Sheet_Metal_(ASM)_Systems Standard for Architectural Sheet Metal (ASM) Systems].
 +
<li>'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the requirements published in [https://rpm.rcabc.org/index.php?title=ASM_Roof_Systems_Standard#Section_9.2._Materials Section 9.2.] of the Standard.
 +
</li></ol>
  
 
<hr>
 
<hr>

Latest revision as of 17:08, 26 October 2023



Division C - Accepted Materials


Zimmerman SS1500
by Cascade Roofing & Exteriors Inc.

The metal panel listed and described below is accepted for use in the RoofStar Guarantee Program.
Manufacturer
Cascade Roofing & Exteriors Inc.
Contact Address
See the current Membership list and contact information at www.rcabc.org
Product Group - Standing Seam Metal Roof System
Panel Machine
Zimmerman
Panel Name
Zimmerman SS 1500
Seam Type
Mechanical Lock

The roofing assembly / material information published below and in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority. For more information about this product or system, consult the manufacturer.

OVERVIEW

The Zimmerman SS 1500 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a standing seam height of 38 mm (1½").

This on–site manufacturing eliminates the need for end laps, with continuous panel forming capabilities in lengths up to 15 – 24 m (50’).

SYSTEM DESCRIPTION

  1. General: Standing seam panels employ a hidden fastening system for securement to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
  2. Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction. Plywood decking is to be nominal 13mm (½") thick or thicker.
  3. Fasteners (Screws): To attach clips to plywood, use #8 x 1" long pancake head, A-point, coated steel screw. Minimum 2 screws per clip. For steel decking or Z-girts, use #8 x 1" long pancake head, having a self-drill and tap point, minimum 2 screws per clip.
  4. Panel Clips: One-piece clip 64 mm (2½") wide by 38mm (1½") high with a 16 mm (5/8") base. The minimum thickness is 22 gauge metal; fastened to a plywood deck 600 mm (24") O.C. Custom-Built 2SS RC1.5" standing seam roof clip.
  5. Deck Requirements: in keeping with the Standard for Architectural Sheet Metal (ASM) Systems.

PROFILE

N/A

TECHNICAL DATA SHEET

N/A

SITE CONDITIONS

Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").

PERFORMANCE REQUIREMENTS

  1. Wind Uplift Resistance: Panel securement shall conform to the requirements in Part 3 of the Standard for Architectural Sheet Metal (ASM) Systems.
  2. Materials:RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the requirements published in Section 9.2. of the Standard.


Back to Site-Formed Metal Roofing Systems

Back to Accepted Materials