Manufacturer: <b>INTERIOR ROOFING LTD.</b>
+
__NOTOC__
 +
__NONUMBEREDHEADINGS__
 +
{| class="wikitable"
 +
|-
 +
| style="background-color: #ffffcc; column-width:100%" | The metal panel listed and described below is accepted for use in the '''''RoofStar Guarantee Program'''''.
 +
|}
 +
{| class="wikitable"
 +
|-
 +
|
 +
;'''Manufacturer''': Interior Roofing (2011) Ltd.
 +
;'''Contact Address''': See the current Membership list and contact information at [http://www.rcabc.org/members/find-a-member/ www.rcabc.org]
 +
;'''Product Group - Standing Seam Metal Roof System'''
 +
;'''Panel Machine''': Series 1000
 +
;'''Panel Name''': Series 1000
 +
;'''Seam Type''': Mechanical Lock
  
Contact Address: See the current Membership list and contact information at [http://www.rcabc.org/members/find-a-member/ '''www.rcabc.org''']
+
The roofing assembly / material information published below and in the [http://{{SERVERNAME}}/index.php?title=Main_Page RCABC Roofing Practices Manual] DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority. For more information about this product or system, consult the manufacturer.
 
+
|}
Product Group: <b>STANDING SEAM METAL ROOF SYSTEM &#8211; SERIES 1000 INTERLOCKING PANEL</b>
 
 
 
;DESCRIPTION
 
  
 +
====OVERVIEW====
 
The Series 1000 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 37.5 mm (1-1/2").  
 
The Series 1000 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 37.5 mm (1-1/2").  
  
 
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
 
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
  
;1.1 <u>GENERAL</u>
+
====SYSTEM DESCRIPTION====
:The roofing assembly / material information published in the <b>RCABC <i>Roofing Practices Manual</i></b> DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
+
#'''General''': Standing seam panels employ a hidden fastening system for securement to a solid substrate. Maximum clip spacing is 450 mm (18") o/c. Panels are seamed together with a mechanical seamer.
 +
#'''Range of application''': on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
 +
#'''Plywood Decking''': The plywood is to be a nominal 15.9 mm (5/8") (19/32") thick, square edged.
 +
#'''Panel Attachment''': Fasteners are fixed through clips that hook onto the male leg of the panel. Spacing is site specific, engineer must confirm fixing specifications.
 +
#'''Fasteners (Screws)''': Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1 ".) long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
 +
#'''Panel Clips''': One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in. (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. <i>Englert</i> &#8220;Series 1000 Interlocking Clip&#8221;
  
;1.2 <u>SYSTEM DESCRIPTION</u>
+
====PROFILE====
:.1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Maximum clip spacing is 450 mm (18") o/c. Panels are seamed together with a mechanical seamer.
+
N/A
:.2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
 
:;.3 <b>Panel Attachment:</b>
 
:;<u>Fasteners (Screws)</u>
 
::Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1 ".) long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
 
:;<u>Roof Deck Fasteners (Panel Clips)</u>
 
::One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in. (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. <i>Englert</i> &#8220;Series 1000 Interlocking Clip&#8221;.
 
:;.4 Plywood Decking: The plywood is to be a nominal 15.9 mm (5/8") (19/32") thick, square edged.
 
  
;1.3 <u>SITE CONDITIONS</u>
+
====TECHNICAL DATA SHEET====
:.1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
+
N/A
  
;1.4 <u>PERFORMANCE REQUIREMENTS</u>
+
====SITE CONDITIONS====
 +
Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
  
:#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
+
====PERFORMANCE REQUIREMENTS====
:#'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php/RoofStar_Guarantee_Standards_for_ASM_Roof_Assemblies Architectural Sheet Metal (ASM) Roof Standards].
+
#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
 +
#'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php/RoofStar_Guarantee_Standards_for_ASM_Roof_Assemblies Architectural Sheet Metal (ASM) Roof Standards].
  
 
<hr>
 
<hr>

Revision as of 16:44, 1 October 2018


The metal panel listed and described below is accepted for use in the RoofStar Guarantee Program.
Manufacturer
Interior Roofing (2011) Ltd.
Contact Address
See the current Membership list and contact information at www.rcabc.org
Product Group - Standing Seam Metal Roof System
Panel Machine
Series 1000
Panel Name
Series 1000
Seam Type
Mechanical Lock

The roofing assembly / material information published below and in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority. For more information about this product or system, consult the manufacturer.

OVERVIEW

The Series 1000 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 37.5 mm (1-1/2").

On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').

SYSTEM DESCRIPTION

  1. General: Standing seam panels employ a hidden fastening system for securement to a solid substrate. Maximum clip spacing is 450 mm (18") o/c. Panels are seamed together with a mechanical seamer.
  2. Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
  3. Plywood Decking: The plywood is to be a nominal 15.9 mm (5/8") (19/32") thick, square edged.
  4. Panel Attachment: Fasteners are fixed through clips that hook onto the male leg of the panel. Spacing is site specific, engineer must confirm fixing specifications.
  5. Fasteners (Screws): Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1 ".) long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
  6. Panel Clips: One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in. (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert “Series 1000 Interlocking Clip”

PROFILE

N/A

TECHNICAL DATA SHEET

N/A

SITE CONDITIONS

Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").

PERFORMANCE REQUIREMENTS

  1. Wind Uplift Standards: Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also Guides and Notes (Wind Resistance) for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
  2. Materials:RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the Architectural Sheet Metal (ASM) Roof Standards.